Deyan Electric is a professional supplier with rich manufacturing experience in industrial electrical appliances. The High/Low Voltage Prefabricated Substation is a compact, fully enclosed, and type-tested solution for 12kV to 400V power distribution. This "plug-and-play" unit integrates a transformer, HV/LV switchgear, and control systems into a single, robust, and weatherproof enclosure. It ensures reliable energy supply, enhanced safety, and is ideal for quick deployment in urban, industrial, and commercial applications
The High/Low Voltage Prefabricated Substation is widely used in urban grid upgrades, residential communities, high-rise buildings, industrial and mining facilities, hotels, shopping malls, airports, railways, oil fields, docks, highways, and temporary power facilities for both indoor and outdoor applications.
The High/Low Voltage Prefabricated Substation is a fully integrated, compact solution for transforming medium voltage (e.g., 12kV or 40.5kV) to low voltage (400V). This "plug-and-play" unit combines transformers, HV/LV switchgear, and control systems in a robust, weatherproof enclosure. It ensures reliable power distribution, enables rapid on-site deployment with minimal civil work, and is ideal for urban, industrial, and renewable energy applications.
Product Parameter ( Specification )
● Load Switch Technical Specifications
Serial Number
Name
Unit
FKN12-12 Load Switch
FZN25-12 Vacuum Load Switch
1
Rated voltage
kV
10
2
Maximum operating voltage
kV
12
3
Rated frequency
Hz
50
4
Rated current
A
630
5
Rated breaking load current
A
630
6
Thermal Stability Current (RMS)
kA/S
20/2
20/4
7
Dynamic Stability Current
kA
50
50
8
Short-circuit closing current (peak)
KA
50
50
9
Full-load breaking cycles
Second
20
10000
10
Mechanical life
Second
2000
10000
11
1 min Power Frequency Withstand Voltage (Phase-to-Phase and Phase-to-Ground)
kV
42
42
12
Lightning impulse voltage (relative and to ground)
kV
75
75
● Technical Specifications for High-Voltage Fuses
Serial Number
Rated Voltage (kV)
Breaking Current (A)
Breaking Current (KA)
Fuse Rating (A)
UK model
Domestic Model
SDL※J
12
40
31.5
6.3 10 16 20 25 31.5 40
SDL※J
XRNT-12
12
100
31.5
50 63 71 80 100
SDL※J
12
125
31.5
125
*Note: Determined by whether a striker is installed. N denotes no striker, A denotes striker present.
Serial Number
Trip Device Type
Rated current of the trip unit A
Breaking Capacity kA (AC 380V)
DW15-630
315,400,630
40
DW15-1000
630,800,1000
50
DW15-1600
Thermal-electromagnetic or electronic
1600
50
DW15-2500
1600,2000,2500
60
CW1-2000
630,800,1000,1250,1600,2000
65(80)
CW1-3200
Intelligent
2000,2500,3200
100
Product Feature And Application
Compact, Integrated "Plug-and-Play" Design
Robust & Weatherproof Enclosure
High Safety & Reliability
Excellent Transformer Performance
Flexible Configuration & Easy Maintenance
Application Sites
◇ Compact secondary substations
◇ Small industrial and mining enterprises
◇ Wind power plants
◇ Hotels, shopping malls, office buildings, commercial centers, etc.
◇ C- Load switch unit
◇ D-Direct cable connection unit
◇ De- Direct cable connection unit with grounding switch